Fuse Board & Consumer Units for homeowners in Bristol
A new consumer unit in a home has to meet current wiring regulations. Units in domestic premises must now be in a non-combustible enclosure, usually steel, or housed in a non-combustible cabinet. Most circuits need 30mA residual current protection, and many electricians now fit RCBOs, which protect each circuit individually so a fault on one circuit does not switch off several others. Surge protection is generally required under the current edition of BS 7671, and arc fault detection devices are recommended in some types of residential building.
Before fitting the new unit, the electrician should test the existing circuits. Old wiring can have insulation faults or shared neutrals that went unnoticed with fuses but will trip an RCD immediately. If testing finds problems, they need fixing before the new unit will work properly, which may add cost. The electrician should also check the main earthing and the protective bonding to gas and water pipes, which often needs upgrading in older homes.